Gas detector AVUS-COMBI

Appointment

Generating alarm signals about exceeding the specified values of pre-explosive concentrations of methane (propane) or mass concentration of carbon monoxide. Generating a signal to engage the output relay or close the gas shut-off valve.

Application
Monitoring and notification of exceeding specified threshold values of monitored gases in residential and administrative buildings, industrial and industrial buildings, in garages, in car parks and parking lots, etc.
Specifications
Parameter Value
Measured gas (monogas) Methane (CH₄),
Propane ( С₃Н₈)
Carbon monoxide (CO)
Measuring range 0 ... 50% LEL (СН₄, С₃Н₈) 0 ... 300 mg / m3 (СО)
Resistance to external factors:
1. Temperature
2. Relative humidity
3. Atmospheric pressure
-10 ... + 40 °С
30 ... 90% at Т = 25 °С
84 ... 106.7 kPa
Limits of acceptable absolute error of operation in the temperature range, absolute, СН₄ ± 2.5% LEL (+15 ... + 25 °С; 30 ... 70% r.h.)
Limits of acceptable absolute error of operation in the temperature range, absolute, С₃Н₈ ± 4% LEL (-10 ... + 15 °С; +25 ... + 40 °С)
Limits of acceptable absolute error of operation in the temperature range, absolute, СО ± 5 mg / m³ for the first alarm threshold ± 20 mg / m³ for the second alarm threshold
Two alarm thresholds 7% and 15% LEL (CH₄, С₃Н₈) 20 and 100 mg / m³ (СО)
Alarm LED, sound
Type of sensor semiconductor
Response time to the presence of the measured gas, max semiconductor (СН₄, С₃Н₈, СО): 30 sec.
Powered by a network adapter, V 12
Power consumption, max, W 2
Average service life, min, years 5
Contact voltage, current / contact resistance 220 V, 0,5 A / 2 Ohm
Dimensions, not less d = 100 mm, h = 50 mm
Weight of gas detector, min 0,25 kg
Advantages
low power consumption;
easy removability;
control function of gas supply shut-off valve;
unified standard, modular based design;
possible to supply the power by «concealed wiring method»;
self-testing function of output signals and indication performance capability.